Ground wires don't go from the pole to the house. Your home's ground literally goes into the ground, either via a stake or by being attached to a cold water pipe. Having your ground connected to distant objects/poles/locations is counterproductive, because the extreme distance is likely to wind up with different potentials at different points, which would put current on the ground wire all the time, which is exactly what you don't want.
Anyway, notice that the big bare wire is not actually electrically connected to anything and is only attached to a tensioner pulling it against the house. The ferrule on the end is to keep it from fraying over time.
It’s called neutral supported cable, the bare support wire is also the houses neutral wire.
Still safe to touch, but it is technically a current carrying wire.
Even though it's neutral, and very close to ground potential... Depending on how much current is flowing through the other two wires, the voltage on the neutral will be varying amounts of non zero. Probably not enough to kill you, but maybe enough to feel bad, under the right circumstances.
That's why, even though the neutral and the ground are bonded together in the breaker panel, you still need to run a separate wire to your outlet to ground your appliances. Electricity doesn't take the easiest path, it takes all paths simultaneously, relative to their resistance, favoring the easiest. Don't make yourself a path 🤷♂️
Still nothing to be afraid of, you shouldn't be messing with it anyway. Just steer clear and you'll be fine.
Note: I'm not an electrician.
The neutral is bonded to ground at the panel, the current is pretty much zero. wires look well insulated, I would feel very comfortable climbing up on a ladder a couple feet away poking it off with a wooden stick.
You're not entirely wrong, but the ground in the panel is better for lightning strikes, and surprisingly bad at sinking actual current meant for the neutral return to the transformer.
That's part of what makes a loose neutral such a fire hazard.
Yes, it's likely safe, and I'd probably put my hand on it without much thought, same with working in a hot panel, the neutral/ground bus is probably fine.
But this is the Internet, if you start making blanket statements about things being safe, you're gonna have a bad time. And some person who doesn't know any better, might have a worse time.
Better to at least acknowledge that there are still dangers, however small.